Know-how Pla­ti­num Resis­tance Ther­mo­me­ter

In indus­tri­al tem­pe­ra­tu­re mea­su­re­ment, pla­ti­num resis­tance ther­mo­me­ters such as Pt100 and Pt1000 stand for the hig­hest pre­cis­i­on, excel­lent long-term sta­bi­li­ty, and relia­ble repea­ta­bi­li­ty. Whe­ther in the labo­ra­to­ry or under deman­ding pro­cess con­di­ti­ons: explo­re our tech­ni­cal know-how sec­tion to learn all about the phy­si­cal prin­ci­ples, com­mon designs, tole­rance clas­ses, and prac­ti­cal cri­te­ria for seam­less­ly inte­gra­ting them into your mea­su­re­ment cir­cuits.

Table of Con­tents: Pla­ti­num Resis­tance Ther­mo­me­ters

What is a Resis­tance Ther­mo­me­ter?

A resis­tance ther­mo­me­ter is a high-pre­cis­i­on tem­pe­ra­tu­re sen­sor desi­gned for low and medi­um tem­pe­ra­tures. The mea­su­red tem­pe­ra­tu­re is deter­mi­ned by the tem­pe­ra­tu­re-depen­dent chan­ge in the elec­tri­cal resis­tance of a metal­lic con­duc­tor. The sens­ing resis­tor used for this pur­po­se is typi­cal­ly made of high-puri­ty pla­ti­num, as it fea­tures high sta­bi­li­ty and excel­lent repea­ta­bi­li­ty.

As the tem­pe­ra­tu­re rises, lat­ti­ce vibra­ti­ons (pho­nons) in the pla­ti­num crys­tal increase. This leads to stron­ger scat­te­ring of the con­duc­tion elec­trons, resul­ting in an increase in elec­tri­cal resis­tance. This phy­si­cal rela­ti­onship forms the basis of tem­pe­ra­tu­re mea­su­re­ment and is stan­dar­di­zed for pla­ti­num resis­tance ther­mo­me­ters in DIN EN 60751. This stan­dard defi­nes refe­rence func­tions that mathe­ma­ti­cal­ly link elec­tri­cal resis­tance to tem­pe­ra­tu­re, allo­wing the mea­su­red resis­tance to be con­ver­ted into the cor­re­spon­ding tem­pe­ra­tu­re (see Tem­pe­ra­tu­re Deter­mi­na­ti­on and Refe­rence Func­tions).

Unli­ke ther­mo­cou­ples, who­se mea­su­re­ment prin­ci­ple is based on a tem­pe­ra­tu­re dif­fe­rence and requi­res a refe­rence junc­tion (cold junc­tion), resis­tance ther­mo­me­ters deter­mi­ne the tem­pe­ra­tu­re direct­ly via the elec­tri­cal resis­tance at the mea­su­ring point.

Types of RTD Sen­sors

The tem­pe­ra­tu­re-depen­dent RTD sen­sor is the cen­tral com­po­nent in a resis­tance ther­mo­me­ter used to deter­mi­ne the tem­pe­ra­tu­re at the mea­su­ring point. Two pri­ma­ry designs are com­mon­ly used:

• Wire-wound sen­sors con­sist of a fine pla­ti­num wire on a cera­mic or glass car­ri­er. They fea­ture high mea­su­re­ment accu­ra­cy, long-term sta­bi­li­ty, and low drift.
• Thin-film sen­sors con­sist of a thin pla­ti­num film on a car­ri­er sub­stra­te. They are more com­pact, mecha­ni­cal­ly robust, and cost-effec­ti­ve.

Nomi­nal Resis­tances

In addi­ti­on to the design, the nomi­nal resis­tance of the RTD ele­ment plays a key role. It is defi­ned by its elec­tri­cal resis­tance at 0 °C, which ser­ves as the refe­rence point. The most com­mon pla­ti­num resis­tors have nomi­nal values of 10 Ω, 100 Ω, 500 Ω, or 1000 Ω (Pt10, Pt100, Pt500, Pt1000).

The choice depends on the appli­ca­ti­on and the spe­ci­fic mea­su­re­ment requi­re­ments:

  • Pt100: The most wide­ly used type in indus­tri­al appli­ca­ti­ons, offe­ring an opti­mal com­pro­mi­se bet­ween mea­su­re­ment vol­ta­ge, self-hea­ting, and lead-wire errors.
  • Hig­her nomi­nal resis­tances (Pt500, Pt1000): Pro­vi­de a lar­ger mea­su­re­ment vol­ta­ge at the same mea­su­ring cur­rent, making them less sen­si­ti­ve to lead-wire resis­tance.
  • Lower nomi­nal resis­tances (Pt10): Enable com­pact, rug­ged designs and gene­ra­te a lower mea­su­re­ment vol­ta­ge at the same mea­su­ring cur­rent, resul­ting in less dis­rup­ti­ve self-hea­ting.

Con­nec­tion Types and Lead-Wire Resis­tances

Along with the design and nomi­nal resis­tance, the cho­sen wiring con­fi­gu­ra­ti­on plays a key role, as lead-wire resis­tance can direct­ly affect tem­pe­ra­tu­re mea­su­re­ment. Resis­tance ther­mo­me­ters are con­nec­ted using 2-, 3-, or 4-wire con­fi­gu­ra­ti­ons. The choice of cir­cuit depends on mea­su­re­ment accu­ra­cy requi­re­ments, trans­mis­si­on distance, and instal­la­ti­on cos­ts.

In a 2-wire con­fi­gu­ra­ti­on, the RTD ele­ment is con­nec­ted to the mea­su­ring instru­ment via two wires. The resis­tance of the lead wires is not com­pen­sa­ted; ins­tead, it adds direct­ly to the resis­tance of the RTD ele­ment, dis­tort­ing the mea­su­re­ment result. While this cir­cuit is simp­le and cost-effec­ti­ve, it is only sui­ta­ble for short distances and low accu­ra­cy requi­re­ments.

Widerstandsthermometer Schema 2-Leiter-Schaltung

In a 3-wire con­fi­gu­ra­ti­on, an addi­tio­nal lead is used to appro­xi­ma­te the lead-wire resis­tance and sub­tract it from the mea­su­red value. This con­fi­gu­ra­ti­on is wide­ly used in indus­tri­al prac­ti­ce, offe­ring a prac­ti­cal balan­ce bet­ween instal­la­ti­on effort and mea­su­re­ment accu­ra­cy.
Resistance Thermometer 3-Wire Circuit Diagram
The 4-wire con­fi­gu­ra­ti­on com­ple­te­ly sepa­ra­tes the cur­rent path from the vol­ta­ge mea­su­re­ment. The mea­su­ring cur­rent flows through the RTD ele­ment via two dedi­ca­ted leads, while the vol­ta­ge drop is mea­su­red direct­ly across the RTD ele­ment through two sepa­ra­te, vir­tual­ly cur­rent-free leads. This vir­tual­ly eli­mi­na­tes the influence of lead-wire resis­tance, deli­ve­ring the hig­hest pos­si­ble mea­su­re­ment accu­ra­cy.
Resistance Thermometer 4-Wire Circuit Diagram

Basic Con­s­truc­tion

An over­view of the various designs and con­fi­gu­ra­ti­ons of ther­mo­cou­ples can be found in our pro­duct over­view.
A pro­duct fin­der is also available the­re to assist you in sel­ec­ting a sui­ta­ble sen­sor.

Typi­cal Appli­ca­ti­ons and Com­pa­ri­son with Ther­mo­cou­ples

Resis­tance ther­mo­me­ters are pre­fer­red when high­ly pre­cise and repro­du­ci­b­le mea­su­re­ments are requi­red in the low to medi­um tem­pe­ra­tu­re ran­ge. Typi­cal appli­ca­ti­ons include power gene­ra­ti­on and the che­mi­cal indus­try, such as for pro­cess and plant moni­to­ring.
Com­pared to ther­mo­cou­ples, resis­tance ther­mo­me­ters offer hig­her mea­su­re­ment accu­ra­cy, excel­lent repea­ta­bi­li­ty, and lower drift.
Ther­mo­cou­ples, on the other hand, are often more cost-effec­ti­ve and par­ti­cu­lar­ly well-sui­ted for appli­ca­ti­ons invol­ving very high tem­pe­ra­tures, seve­re mecha­ni­cal stress, or fast tem­pe­ra­tu­re chan­ges, while cove­ring a signi­fi­cant­ly wider tem­pe­ra­tu­re ran­ge.
The choice bet­ween a resis­tance ther­mo­me­ter and a ther­mo­cou­ple the­r­e­fo­re lar­ge­ly depends on the spe­ci­fic requi­re­ments for tem­pe­ra­tu­re ran­ge, mea­su­re­ment accu­ra­cy, and robust­ness.

Tem­pe­ra­tu­re Deter­mi­na­ti­on and Refe­rence Func­tions

In Euro­pe, tem­pe­ra­tu­re deter­mi­na­ti­on using resis­tance ther­mo­me­ters is typi­cal­ly based on DIN EN 60751. This stan­dard defi­nes refe­rence func­tions R(T) that mathe­ma­ti­cal­ly link resis­tance R to tem­pe­ra­tu­re T. The­se refe­rence func­tions are descri­bed by poly­no­mi­al equa­tions and repre­sent the (modera­te­ly) non-line­ar rela­ti­onship bet­ween elec­tri­cal resis­tance and tem­pe­ra­tu­re.Widerstandsthermometer PolynomfunktionThe nomi­nal resis­tance R0 as well as the coef­fi­ci­ents A and B are nor­ma­tively defi­ned. Based on the­se refe­rence func­tions – or their inver­se func­tions – the cor­re­spon­ding mea­su­red tem­pe­ra­tu­re can be deter­mi­ned from the mea­su­red resis­tance.

Resis­tance Cha­rac­te­ristic of the Refe­rence Func­tion for a Pt100

Widerstandsverlauf Pt100

Limit Devia­ti­ons

The per­mis­si­ble limit devia­ti­ons for indus­tri­al pla­ti­num resis­tance ther­mo­me­ters are defi­ned in DIN EN 60751. The stan­dard dif­fe­ren­tia­tes bet­ween accu­ra­cy clas­ses AA, A, B, and C, each with vary­ing requi­re­ments for mea­su­re­ment accu­ra­cy.
The per­mis­si­ble tem­pe­ra­tu­re ran­ge in each case depends on both the design of the RTD ele­ment (wire-wound or thin-film) and the sel­ec­ted accu­ra­cy class. The cor­re­spon­ding limit devia­ti­ons are sum­ma­ri­zed in the fol­lo­wing table.

Class Tem­pe­ra­tu­re ran­ge
Wire-wound resis­tors
Tem­pe­ra­tu­re ran­ge
Thin-film resis­tors
Limit Devia­ti­on

Class AA

-50 to 250 °C

0 to 150 °C

± (0,1 + 0,0017 │ T │) °C

Class A

-100 to 450 °C

-30 to 300 °C

± (0,15 + 0,002 │ T │) °C

Class B

-196 to 600 °C

-50 to 500 °C

± (0,3 + 0,005 │ T │) °C

Class C

-196 to 600 °C

-50 to 600 °C

± (0,6 + 0,01 │ T │) °C

Typi­cal Sources of Error

When mea­su­ring tem­pe­ra­tu­re with resis­tance ther­mo­me­ters, various sources of error can lead to dis­tor­ted or unre­lia­ble mea­su­re­ment results. The most important cau­ses are sum­ma­ri­zed below:

Incor­rect nomi­nal resis­tance set on the mea­su­ring instru­ment
Resis­tance ther­mo­me­ters are defi­ned by their nomi­nal resis­tance at 0 °C and the cor­re­spon­ding cha­rac­te­ristic cur­ve. If an incor­rect nomi­nal resis­tance is con­fi­gu­red in the mea­su­ring instru­ment, this leads to an erro­n­eous con­ver­si­on of the mea­su­red resis­tance value into tem­pe­ra­tu­re.

Sources of error in 2-wire mea­su­re­ments
In a 2-wire con­fi­gu­ra­ti­on, the lead-wire resis­tance is ful­ly mea­su­red and super­im­po­sed on the actu­al RTD ele­ment resis­tance. In the case of long con­nec­tion cables with high lead resis­tances com­bi­ned with low nomi­nal resis­tances of the RTD ele­ment (espe­ci­al­ly Pt10), this can lead to sub­stan­ti­al tem­pe­ra­tu­re mea­su­re­ment errors.

Sources of error in 3-wire mea­su­re­ments
The 3-wire con­fi­gu­ra­ti­on assu­mes that all con­nec­ted lead wires have iden­ti­cal elec­tri­cal resis­tances. Any devia­ti­ons bet­ween the leads result in inac­cu­ra­te com­pen­sa­ti­on of the lead-wire resis­tance, lea­ding to mea­su­re­ment errors.

Self-hea­ting of the sens­ing ele­ment
The mea­su­ring cur­rent cau­ses self-hea­ting of the RTD ele­ment. This effect increa­ses with hig­her curr­ents and lar­ger nomi­nal resis­tances (espe­ci­al­ly Pt500 and Pt1000) and can result in an arti­fi­ci­al­ly ele­va­ted tem­pe­ra­tu­re rea­ding.

Inho­mo­genei­ties or con­ta­mi­na­ti­on in the RTD ele­ment
Impu­ri­ties or struc­tu­ral inho­mo­genei­ties in the pla­ti­num can alter the tem­pe­ra­tu­re-depen­dent resis­tance cha­rac­te­ristic of the RTD ele­ment. Con­se­quent­ly, the rela­ti­onship bet­ween resis­tance and tem­pe­ra­tu­re no lon­ger com­pli­es with the stan­dar­di­zed refe­rence func­tion, resul­ting in incor­rect tem­pe­ra­tu­re rea­dings.

Mecha­ni­cal stress and aging
Vibra­ti­ons, mecha­ni­cal stres­ses, or repea­ted ther­mal cycling can alter the struc­tu­ral inte­gri­ty of the RTD ele­ment. This may chan­ge the resis­tance cha­rac­te­ristic and lead to tem­pe­ra­tu­re mea­su­re­ment errors (as descri­bed abo­ve).

Poor ther­mal cou­pling
Insuf­fi­ci­ent ther­mal cou­pling bet­ween the tem­pe­ra­tu­re sen­sor and the medi­um to be mea­su­red impairs heat trans­fer. This can lead to slug­gish respon­se times or mea­su­re­ment errors.